We
recommend M-System Analog Backup Station, Model JB. The JB accepts 4-20 mA (CAS input) and passes it through to output as 4-20 mA
(MV output) in normal operating conditions. Please refer to the circuit diagram (Figure 1). When the external MAN command
relay (terminal 8) is closed, the JB turns to manual control mode (MODE 3). In
this mode you can hold the output at a specific preset value (like 4 mA). If you
need to change the hold value on site, then you can use the Programming Unit,
PU-2A. As for other manual control modes, please refer to the descriptions below: When the external MAN command relay is closed, the JB turns on to manual control
mode. Actual output signal is determined by following three operation mode.
MODE 1 : Hold the CAS control signal at the moment of the MAN command. MODE 2 : Go back the preset time period and hold the CAS control signal at that
moment. MODE 3 : Hold a specific value preset by the Programming Unit (PU-2A).
|
In each mode, the output can be manipulated with external
UP or DOWN commands (Figure 2). When the MAN command relay is opened, the CAS
control signal is recovered with smooth transition. |
Figure 1. JB circuit diagram. |
|
Figure 2. JB manual control function. |
|