L.S.P. E
26/28

DISCUSSIONMA-100, MA-200MAX-100, MAX-200MMAH-100, MMAH-200BREAKERBE SURE TOINSTALL THEBREAKER.SURGEABSORBERELEMENTBBASE SOCKETMAIN BODY41827635DISCHARGEELEMENTPOWERSOURCE(SURGE SIDE)PROTECTEDEQUIPMENT(LOAD SIDE)ALARM OUTPUTBASE SOCKETELEMENTGROUND TERMINAL2A2A45817632HF FILTERDISCHARGEELEMENTTO CABLETO EQUIPMENTALMBREAKERBE SURE TOINSTALL THEBREAKER.BUuVvGTOEQUIP-MENTPOWERSOURCE(SURGE SIDE)DISCHARGEELEMENTINDI-CATORCIRCUITVOLTAGELIMITCIRCUIT26QUESTIONIs power supply line safe if the surge protector for the power source damaged?Yes, because the surge protectors have internal protection circuits.11ANSWERANSWERThere is a chance that incorporated element of the surge protector has closed-circuit failure when the surge protector receives stress from lightning surge for a long time or handle lightning surge that exceeds discharge withstand current rating. At that time, power source line might have short circuit accident or surge protector might have heat accident. Therefore, surge protectors have a protection circuit that cut off the element. However, it might not be able to handle when a surge protector receives lightning surge which far exceeds discharge withstand current rating such as a direct lightning strike. Be sure to set an electric current breaker on power source line.

元のページ 

10秒後に元のページに移動します

※このページを正しく表示するにはFlashPlayer10.2以上が必要です